Almost every sizing mistake in solar comes from confusing two different quantities. Your array is sized by energy: kilowatt-hours over a year. Your inverter is sized by power: the most watts you will ever draw at one instant, plus the surge of whatever motor happens to start at that moment. Size an inverter from your daily kWh and it will trip the first time the fridge and the microwave overlap.

The two numbers you need

Continuous rating must cover the sum of everything running simultaneously. Surge rating must cover that total minus your largest motor's running watts, plus that motor's starting watts.

Written out: Surge needed = (total running watts − largest motor's running watts) + largest motor's starting watts

LoadRunning WStarting W
Refrigerator150600
LED lighting6060
Wi-Fi and devices7575
Well pump (1 HP)1,0004,000
Total running1,285
Surge needed4,285

A 1,500W inverter covers the running total comfortably and fails instantly. You need roughly 2,000W continuous with a genuine 5,000W surge — and the surge rating matters more here than the continuous one.

Read the surge spec properly

Manufacturers quote surge alongside continuous output, but the duration is what counts. A unit rated for 2x surge over 100 milliseconds may not survive a motor start that draws for two full seconds. Look for the time the surge rating is held, not just the peak number — this is the single most common reason an adequately-specified inverter fails in practice.

If the datasheet does not state surge duration, treat that as a warning about the product rather than an oversight.

Grid-tied sizing is a different calculation

For a grid-tied system with no battery, the inverter is sized to the array, not to your loads — the grid handles your loads. The convention is a DC-to-AC ratio of about 1.2, so an 8.2 kW array pairs with a 6.5-7 kW inverter. Panels rarely produce their rated output, so the inverter clips a handful of peak hours a year in exchange for costing meaningfully less.

There is a hard ceiling to check: on a standard 200A service, interconnection rules typically cap backfed inverter output near 7.6 kW regardless of your array size. That is covered in solar panel sizing for a 200 amp service, and it has ended more than one oversized plan.

Off-grid and backup sizing

Here the inverter must serve your loads directly, so it is sized from the appliance list using the surge formula above. Two more considerations:

  • Do not oversize carelessly. Inverters draw idle power just being switched on — often 20-50W. A 12 kW inverter idling to serve a 300W load wastes real energy every hour of every day.
  • Match it to the battery. A 6 kW inverter needs a battery bank that can actually deliver 6 kW; a small bank with a low discharge rating will sag or shut down under a load its inverter could technically handle.
  • Consider a soft starter before buying a bigger inverter. Cutting a well pump's surge by 50-70% for $150-400 is far cheaper than the inverter capacity it saves you buying — see well pump sizing.

Work it out for your own house

Our free wattage calculator does the surge arithmetic across your appliance list, including well pumps, furnace blowers and sump pumps, and returns both figures. Then the inverter role page turns them into a target spec, and the full sizing sequence shows how the inverter fits alongside the array and the battery.

Confirm the final figure with a licensed electrician before ordering. Inverter sizing interacts with your service panel and your load calculation, and that is not a good place to estimate.